Jump to Navigation

Honeywell 2000 Series Herculine ® Actuators

Herculine ® Actuators
2000 Series

Honeywell’s HercuLine® 2000 series actuators are low torque, precision electric actuators incorporating all of the easy-to-use, high quality, and reliable features of the traditional HercuLine® actuators.

Ensuring processes operate at maximum efficiency, with minimal downtime, and lowest lifetime cost requires precision and high reliability Herculine® actuators. They are industrial rated and engineered for very precise positioning of dampers and valves. They perform especially well in extremely demanding environments requiring continuous duty, high reliability, and low maintenance.

HercuLine 2000 actuators are used in on/off power to open/close or position proportional with 135 or 1000 ohm feedback applications.

HercuLine® 2001 and 2002 Smart actuators are used in current proportional or digital control applications. Access to all actuator parameters for real-time business and maintenance decisions is standard through Modbus RTU, local display, or via HercuLink® Palm PDA software.

HercuLine® 2002 actuators have additional standard features such as non-contact position sensing and slidewire emulation output.

• Motor - no burn out motor can be stalled up to 100 hours without damage to the actuator.
• Duty Cycle- continuous duty cycle
• Any position mounting – the actuator may be mounted in any orientation without degrading performance.
• Power Requirements – Low power consumption 120/240 Vac, 50/60 Hz, single phase ≤0.6/0.3 Amp.
• Enclosure – Rugged, Die cast aluminum NEMA 4X industrial grade enclosure.
• Low Maintenance – Simple proven design means high reliability/low maintenance.
• Limit Switches – Two end-of-travel electric limit switches are supplied as standard equipment with all Herculine® 2000 series actuators
• Warranty – Exceptional warranty
• Certification-CSA (pending),UL,CE

Select a link under the "item" tab below to order.

Table 1
XXXX
Table 1KEY NUMBER - Motor Selection
2000Basic Motor Unit (no electronics)
2001Basic Motor Unit plus Digital Electronics
2002Enhanced Performance Motor Unit with Non-contact Position Sensing
2003Unidirectional Motor (M640D Replacement)

Physical:

Weight: 25 lb. (11.36 kg)
Enclosure: Precision-machined die cast aluminum housing, finished in light gray powder coat epoxy.
Gear Train: Alloy steel, high efficiency steel spur gear primary train. Precision ground, self-locking/self releasing worm gear final mesh.
Storage Temperature: –40 °C to +93 °C (–40 °C to +200 °F)
Relative Humidity: 0 % to 99 % R.H. non-condensing over the full operating temperature range.
Scale: 0 % to 100 % corresponding to full crank arm travel.
Output Shaft: 0.625+/-.005 in (15.88 +/-.13mm) diameter (round)
Rotation: 90° or 150° degrees between 0 % and 100 % on scale, limited by mechanical stops.
Lubrication: Texaco Starplex 2 EP Grease
Output Torque/Full Travel Stroking Time: Torque lb-in (N M) 50 Hz (90°/150°) 60 Hz (90°/150°)
50 / (6.0) 4.5 / 7.5 4 / 6
100 / (11.5) 9 / 15 7 / 12
200 / (22.5) 18 / 30 15 / 25
400 / (45.0) 36 / 60 30 / 50
400 / (45.0) 54 / 90 45 / 75

Electrical:

Mains Supply: 100-130 Vac single phase, 50 Hz or 60 Hz 200-240 Vac single phase, 50 Hz or 60 Hz
Motor: Instant start/stop, non-coasting, non-burnout, continuous duty, permanent magnet, synchronous induction motor. Can be stalled up to 100 hours without damage.
Motor Current: = No load = full load = locked rotor = 0.4 amp for 120Vac, 0.2 amp for 240 Vac
Loss of Power: Stays in place on loss of power
Certifications:
Approvals: CSA/UL (Standard) CE Compliant (optional)
Enclosure Rating: Type 4 (NEMA 4), IP66 (standard)
Torque Settings of Crank Arm Bolts:
Clamp Bolt: 88 lb-in (10 N-m)

Electrical and Performance:

Input Signals: 120 Vac drive open/120 Vac drive close
240 Vac drive open/240 Vac drive close
Operating Temperature: -40°C to +85 °C (-40°F to +185 °F)
Position sensing: Optional dual 1000 ohm film potentiometers
Direction of Rotation: Wire swap


Main menu 2