Jump to Navigation

Schneider Electric MP-54xx Series Electronic Positive Positioning Hydraulic Actuator

Electronic Positive Positioning Hydraulic Actuator
MP-54xx Series

These actuators provide electronic proportional control of dampers, valves, or program switches requiring the return to normal position upon power interruption.

• Proportional control by variable Vdc input signal.
• Compatibility with 2 to 15 Vdc TAC System 8000 input signals.
• Spring return.
• Fixed 3 Vdc operating span.
• Adjustable 2 to 12 Vdc start point for paralleling or sequencing of actuators.
• 10,000 or greater input impedance.
• 24 Vac, 120 Vac, and 240 Vac models.
• Damper models with linkage or base models that require separate damper or valve linkage.

Select a link under the "item" tab below to order.

Cat #WattsVATo ExtendTo RetractRetract on Power LossTorque Rating lb-in. (N-m)AC Voltage +10/-15%Positive Positionera
MP-5430181060301515 (1.69)120Yes
MP-5433181060301515 (1.69)240Yes
Inputs: Compatible with 2 to 15 Vdc from TAC System 8000 controllers
Operating span: Approximately 3 Vdc fixed
Start point: Adjustable 2 to 12 Vdc. Factory set at 6 Vdc. Impedance 10,000° or greater
Power: Refer to Damper Actuators Table and Valve Actuators Table
Connections: Color-coded 4 ft (1.2 m) leads
Outputs:
Electrical: Internal Power Supply: 20 Vdc, 25 mA
Mechanical: Stroke, Damper: Approximately 2 in. (51 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully extended) input range (includes AM-601 linkage)
Stroke, Valve: Approximately 9/16 in. (14 mm) over a nominal 6 Vdc (fully retracted) to 9 Vdc (fully extended) input range
Nominal Damper Area: Actuator sizing should be done in accordance with damper manufacturer's specifications
Environmental:
Ambient temperature limits: Operating: -20 to 140°F (-29 to 60°C)
Damper: -20 to 140°F (-29 to 60°C)
Valve: Refer to Maximum Allowable Ambient Air Temperature for Valve Actuators
Humidity: 5 to 95% RH, non-condensing
Location: NEMA Type 1
Dimensions: 6-3/4 H x 3-23/32 W x 3-1/4 D in. (171 x 18 x 83 mm)
Agency Listings:
UL: UL873 File E9429 Temperature Indicating and Regulating Equipment
CUL: Canadian Standard (File #LR3728)
European Community: EMC Directive 89/336/EEC, Low Voltage Directive 72/23/EEC
General Instructions: Refer to F-24788


Main menu 2