Flowline XP88/89 Series EchoSafe® Ultrasonic Explosion-Proof Level Transmitter

EchoSafe® Ultrasonic Explosion-Proof Level Transmitter
XP88/89 Series

The explosion proof, two-wire ultrasonic transmitter provides non-contact level measurement up to 10 m in hazardous bulk storage, day tank, and sump applications, and is well suited for challenging corrosive, slurry or waste water Media. Application examples include sodium hypochlorite, waste water and resin. The integral display and push button module enable fast and simple calibration.

• Compact XP enclosure with viewing window and dual conduit ports
• Narrow 3” beam diameter enables flexible installation in applications with limited measurement space
• Rugged corrosion resistant PVDF transducer and process mount
• Fail-safe intelligence with diagnostic feedback for easy troubleshooting
• Display indicates air gap of level height distance in inch or centimeter

Flowline Website

Select a link under the "item" tab below to order.

Table 1Table 2
XXX
Table 1Sensor range
887.5 m (24.6’)
8910 m (32.8’)
Table 2Process mount (1)
0NPT (US)
Range XP88: 8” to 24.6’ (20 cm to 7.5 m) XP89: 8” to 32.8’ (20 cm to 10 m)
Accuracy ± 0.2% of max. range
Resolution 0.079” (2 mm)
Beam width 3” (7.6 cm) dia.
Dead band XP88: 8” (20 cm) XP99: 8” (20 cm)
Display type LCD, 6-digit
Display units Inch, cm, ft, m, percent
Memory Non-volatile
Supply voltage 18-28 VDC (loop)
Loop resistance 250Ω max @ 24 VDC
Signal output 4-20 mA , two-wire
Signal invert 4-20 mA or 20-4 mA
Calibration Push button (3-button)
Fail-safe 4 mA, 20 mA, 21 mA, 22 mA or hold last
Process Temp. F: -4° to 140° C: -20° to 60°
Temp. comp. Automatic
Electronics temp. F: -40° to 160° C: -40° to 71°
Pressure 30 psi (2 bar)
Enclosure rating NEMA 4
Enclosure mat. Aluminum
Window mat. Glass
Transducer mat. PVDF
Process mount 2” NPT
Conduit entrance Dual, 1/2” NPT
Compliance RoHS
Classification Explosion proof
Approvals FM: Class 1, Div 1, Groups A, B, C, D Class II/III, Div 1, Groups E, F, G


Main menu 2