Jump to Navigation

Flowline DL14 Series EchoPod® Ultrasonic Level Switch, Controller and Transmitter

EchoPod® Ultrasonic Level Switch, Controller and Transmitter
DL14 Series

The general purpose, ultrasonic sensor provides non-contact level detection up to 49.2” (1.25m) with 4 SPST 60 VA 1A relays and a two-wire 4-20 mA level measurement output. Each relay can be configured on a single set point alarm or latched on two sets for automatic fill or empty in simplex or duplex control modes with fail-safe logic. The embedded controller can replace external control hardware. The sensor is well suited for a wide range of corrosive, sticky or dirty type media. EchoPod is broadly selected for small atmospheric day tank, skid or process vessel, lift station, IBC, drum and sump applications. To configure EchoPod, download our free WebCal software and purchase one USB interface tool.

• Multi-function sensor provides 4-20 mA measurement, relay switch and control functions
• Compact sensor with 2” beam width and 2” dead band optimized for small tank applications
• Four 1A relays programmable for switch or advanced pump or valve control and fail-safety
• Control / switch point functions include:
  • 2 pumps with 2 alarms
  • 1 pump with 3 alarms
  • 2 pumps (lead-lag) with 2 alarms
  • 2 pumps (duplexing) with 2 alarms
  • 4 independent switch point alarms
• Rugged PVDF transducer and polycarbonate enclosure rated 6P for corrosive media

Select a link under the "item" tab below to order.

Table 1
X
Table 1Fob USB interface (2)
0Without Fob
1With Fob
Range 49.2” (1.25 m)
Accuracy 0.125” (3 mm)
Resolution 0.019” (0.5 mm)
Beam width 2” (5 cm)
Dead band 2” (5 cm)
Supply voltage 24 VDC (loop)
Loop resistance 400Ω max
Consumption 0.5W
Signal output 4-20 mA , two-wire (when loop powered)
Contact type (4) SPST relays 1A
Loop fail-safety 4 mA, 20 mA, 21 mA 22 mA or hold last
Relay fail-safety Power loss: Hold last Power on: Open, close or hold last
Hysteresis Selectable
Configuration WebCal® PC Windows® USB 2.0
Temp. comp Automatic over range
Process Temp.:F 20° to 140° C: -7° to 60°
Ambient Temp.:F -31° to 140° C: -35° to 60°
Pressure MWP = 30 PSI
Enclosure Type 6P encapsulated, corrosion resistant & submersible
Encl. material PC/ABS FR
Strain relief mat. Santoprene
Trans. material PVDF
Cable length 48” (1.2 m)
Cable jacket mat. Polyurethane
Process mount 1” NPT (1” G)
Mount. gasket Viton®
Classification General purpose
Approvals CE, cFMus


Main menu 2