Fireye MP100, MP100E, MP101, MP102, MP102E, MP230, MP230H, MP560, MP561, and MP562 Programmer Modules

Fireye
Programmer Modules
MP100, MP100E, MP101, MP102, MP102E, MP230, MP230H, MP560, MP561, and MP562
The Fireye MP100, MP100E, MP101, MP102, MP102E, MP230, MP230H, MP560, MP561 and MP562 Programmer Modules are used with the Fireye Modular M-Series II control. The operational characteristics of the control are determined by the selection of the programmer module (e.g. re-ignition, 2-stage capability, pilot cutoff, etc.). The programmer module incorporates a plug-in design for easy installation. Some programmer modules (MP230, MP230H, MP560, MP561, and MP562) are equipped with a series of dipswitches to select Purge Timing. Pilot Trial for Ignition (PTFI) Timing, and Recycle or Non-Recycle operation. LED indicator lights are on all programmer modules, indicating the operating status of the control. A “check-run” switch is provided on the MP560, MP561 and MP562 programmer modules to assist in testing size and stabilization of the pilot. Flame Failure Response Time (FFRT) is determined by the selection of the amplifier module. Test jacks are also provided on the flame amplifier module to permit flame signal measurement during operation. For proper and safe application of this product, you must refer to Fireye bulletin C-4000 or C-4000E for a detailed description of the various programmer modules, including installation instructions, amplifier selection, operating sequences for each programmer module, etc.

Select a link under the "item" tab below to order.

ItemDescriptions
MP100/MP100ERelight operation.
MP101Same as MP100, except will ignore flame signal in off cycle.
MP102/MP102EOperates like the MP100, except the standing pilot and relight features are eliminated. Ignition safety time is 5 seconds. Control will lockout on flame failure.
MP230Selectable purge timing, trial-for-ignition timing, and recycle/non-recycle operation.
MP230HSelectable purge timing, trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition. For use with two-stage burners.
MP560Selectable purge timing, pilot-trial-for-ignition timing, pilot stabilizing period, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch.
MP561Selectable purge timing, pilot-trial-for-ignition timing, and recycle/non-recycle operation. 10 second main flame trial-for-ignition, check-run switch.
MP562Same as MP560, with lockout on loss of air flow. Non-recycle operation. Programmers with the suffix “E” (e.g. MP100E) are for use with the MC230 and MC230R chassis only.