Jump to Navigation

Precision Digital PD689 5 Digit Loop-Powered Rate/Totalizerr

5 Digit Loop-Powered Rate/Totalizerr
PD689

Through significant innovation in technology and design, we developed the Loop Leader® Series of loop-powered rate/totalizers, which are loaded with standard features and built for tough industrial environments.

Full Featured - Everything comes standard with these meters. The competition may charge extra for loop-powered backlighting, open collector output and programmable exponent capability, but these and a host of other key features are standard on these indicators.

Install Just About Anywhere - Indoors, outdoors, bright sunlight, dimly lit plant, wet, dirty, hot or cold, these indicators go just about anywhere. Their shallow-depth case, FM Type 4X front, loop-powered backlighting, and wide operating temperature range are all standard features. And the PD689 with its FM Approval and CSA Certification can be installed in just about any hazardous location.

Alternating Rate/Total Display - Press Enter/ACK button to alternate between rate and total or program the totalizer so the display automatically changes between displaying rate and total every 10 seconds. This feature is particularly useful if the meters are mounted inside a NEMA 4X or an explosion-proof enclosure.

Square Root Function - The square root extraction feature displays flow rate by extracting the square root from a differential pressure transmitter signal. The user selectable low-flow cutoff feature gives a reading of zero when the flow rate drops below a user selectable value.
• Displays Flow Rate
• User Selectable Low-Flow Cutoff
• Only 2 Calibration Points Required

• 4-20 mA Input
• 5 Digit LCD, 0.6" (15.2 mm) High
• Overflow Feature Displays Total up to 8 Digits
• Programmable Alternating Rate/Total Display
• FM Type 4X, IP65 Front
• Shallow Depth Case 3.2" Behind Panel
• 2 V Drop (5.7 V with Backlight)
• Loop-Powered Backlight Standard
• Custom Engineering Units & Bargraph
• Linear, Square Root, or Programmable Exponent
• Maximum & Minimum Display
• Operating Temperature Range -20 to 65°C
• Intrinsically Safe & Non-Incendive
• Open Collector Alarm or Pulse Output
• HART Protocol Transparent

Select a link under the "item" tab below to order.

Cat #Descriptions
PD689-0K1Loop Leader® PTH - Rate/Totalizer FM & CSA
General
Display: 5 digit LCD (-99999 to 99999), 0.60" (15.2 mm) high, 7-segment, automatic lead zero blanking.
Engineering Units: 0.25" (6.4 mm) high, 14-segment
Bargraph: 20-segment, 0-100% indication
Trend Arrows: Up and down trend indication
Backlight: Bright orange LED (intensity varies with signal)
Front Panel: FM Type 4X, IP65; panel gasket provided
Display Update Rate: 2.5/second
Overrange: Display flashes 99999
Underrange: Display flashes -99999
Programming Method: Four front panel buttons
Noise Filter: Programmable from 1 to 199
Recalibration: Recommended at least every 12 months
Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
Password: Programmable password restricts modification of programmed settings.
Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Voltage Drop: 2.0 V max w/o backlight, 5.7 V max with backlight
Equivalent Resistance: 100 Ω @ 20 mA without backlight, 285 Ω @ 20 mA with backlight.
Normal Mode Rejection: 64 dB at 50/60 Hz
Operating Temperature Range: -20 to 65°C
Allowable Temperature Range: -40 to 65°C*
* Below -20°C the LCD becomes less readable.
Storage Temperature Range: -40 to 85°C
Relative Humidity: 0 to 90% non-condensing
Connections: Screw terminals accept 12 to 22 AWG wire
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: gray
Mounting: 1/8 DIN panel cutout required. Two panel mounting bracket assemblies provided.
Tightening Torque: 4.5 lb-in (0.5 Nm) Screw terminal connectors
Overall Dimensions: 4.68" x 2.45" x 3.79" (119 x 62 x 96 mm)
Weight: 5.7 oz (162 g)
Warranty: 3 years parts and labor
Extended Warranty: 1 or 2 years, refer to Price List for details
Input
Input Range: 4-20 mA
Accuracy: ±0.03% of span ±1 count, square root and programmable exponent: 10-100% FS.
Calibration: Scale without signal or calibrate with signal source
Calibration Range: User programmable over entire range of meter
Minimum Span: 0.40 mA between input 1 and input 2
Input Overload: Over current protection to 2 A maximum
Decimal Point: Up to 4 places (d.dddd, dd.ddd, ddd.dd, dddd.d, or ddddd)
Function: Linear, square root, or programmable exponent
Low-Flow Cutoff: -99999 to 99999 (-99999 disables cutoff function)
Temperature Drift: 50 PPM/°C from -40 to 65°C ambient
Totalizer Features
Total Display: 0 to 99,999 main total display plus 0 to 999 total overflow for a combined 8 digit total of 99,999,999.
Alternating Display: Totalizer may be programmed to alternate between rate and total every 10 seconds.
Time Base: Seconds, minutes, hours, or days
Totalizer Conversion Factor: 0.0001 to 99999
Totalizer: Calculates total based on rate, time base of second, minute, hour, or day, and field programmable multiplier; stored in non-volatile memory upon power loss.
Totalizer Rollover: Total rolls over when total exceeds 99,999,999.
Totalizer Reset: Manual reset or automatic with time delay, or disabled for non-resettable total applications.
Open Collector Output
Rating: Isolated open collector, 30 VDC @ 175 mA maximum
Alarm Output: Assign to rate or total, high or low rate alarm.
Deadband: 0-100% FS, user selectable
Automatic Reset: Alarm resets automatically when signal reaches the reset point.
Pulse Output: K-Factor programmable from 0.0001 to 99999.
Programmable frequency: 2, 4, 8, 16, 32, 64, 128 Hz.
Minimum pulse width: 3.9 ms @ 128 Hz.
Maximum pulse width: 250 ms @ 2 Hz.