Jump to Navigation

Schneider Electric TC-5231 Series, TC-5232, TC-5241 Series Low Temperature Thermostats

Low Temperature Thermostats
TC-5231 Series, TC-5232, TC-5241 Series

The TC-5231, TC-5232, and TC-5241 low temperature thermostats are used to control temperature in air conditioning or refrigeration systems.

• 20 ft. (6.1 m) element senses temperature over a large area. Control responds to coldest one-foot section of the sendor.
• Adjustable setpoint with 5 F degrees (3 C degrees) fixed differential.
• SPST, SPDT and DPST versions.
• Capillary mounting clips provided.

 

 

 

Select a link under the "item" tab below to order.

Cat #Setpoint RangePilot Duty (VA)Voltage (Vac)Full Load AmpsLocked Rotor AmpsNon-inductive (amps)Device TypeElectrical Switch
TC-523135 to 60°F (1.7 to 1.5°C)10024b--16Low temp auto resetSPDTª
TC-523135 to 60°F (1.7 to 1.5°C)7201201710224Low temp auto resetSPDTª
TC-523135 to 60°F (1.7 to 1.5°C)7202081710224Low temp auto resetSPDTª
TC-523135 to 60°F (1.7 to 1.5°C)720240c1710224Low temp auto resetSPDTª
TC-523135 to 60°F (1.7 to 1.5°C)-277--7.2Low temp auto resetSPDTª
TC-523235 to 60°F (1.7 to 1.5°C)10024 b--16Low temp auto resetSPDTª
TC-523235 to 60°F (1.7 to 1.5°C)1251202414424Low temp auto resetSPDTª
TC-523235 to 60°F (1.7 to 1.5°C)1252082414424Low temp auto resetSPDTª
TC-523235 to 60°F (1.7 to 1.5°C)125240 c2414424Low temp auto resetSPDTª
TC-523235 to 60°F (1.7 to 1.5°C)-277--7.2Low temp auto resetSPDTª
TC-524135 to 60°F (1.7 to 1.5°C)10024 b--16Low temp manual resetSPDTª
TC-524135 to 60°F (1.7 to 1.5°C)7201201710224Low temp manual resetSPDTª
TC-524135 to 60°F (1.7 to 1.5°C)7202081710224Low temp manual resetSPDTª
TC-524135 to 60°F (1.7 to 1.5°C)720240 c1710224Low temp manual resetSPDTª
TC-524135 to 60°F (1.7 to 1.5°C)-277--7.2Low temp manual resetSPDTª
TC-524215 to 55°F (-9.4 to 12.8°C)1251201696-Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)1252089.255.2-Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)125240 c848-Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)125277--7.2Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)1251206366Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)1252083.420.46Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)125240 c3186Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
TC-524215 to 55°F (-9.4 to 12.8°C)125277--6Low temp manual reset1-SPST Main N.C. 1-SPST Aux N.O.
Setpoint adjustment range: Dual marked 35 to 60°F (1.7 to 15.5°C). TC-5242: 15 to 55°F (-9.4 to 12.8°C)
Sensing element: Vapor pressure type, copper construction
Differential: 5 F degrees (3 C degrees) fixed
Electrical switch: Refer to Model Chart
Ratings: Refer to Model Chart
Connections: Coded screw terminals
Mounting: In any position on any surface not subject to excessive vibration
Housing: Molded gray PVC plastic cover with a zinc-plated steel main enclosure with a 1/2 in. conduit opening.
TC-5242: painted steel housing
Environment:
Ambient temperature limits: Shipping: -40 to 150°F (-40 to 66°C).
Operating: Must be 5°F (3°C) above setpoint to a maximum of 150°F (66°C) at case.
Thermal sensing element: 300°F (149°C).
Humidity: Enclosure: 5 to 95% RH, non-condensing.
Thermal sensing element: 0 to 100% RH.
Locations: NEMA Type 1
Dimensions:
Case: 2-45/64 H x 3-1/2 max. W x 2 max. D in. (69 x 89 x 51 mm). TC-5242: 3-1/4 H x 4 L x 2 D in. (83 x
101 x 51 mm)
Element: 3/32 in. O.D. x 20 ft. length (2.4 mm x 6.1 m). TC-5242 1/8 in. O.D. x 20 ft. length. (3.2 mm x 6.1 m)
Agency Listings:
UL 873: Underwriters Laboratories Inc. listed (File # E9429 Category Temperature-indicating and Regulating
Equipment)
CSA: Certified for use in Canada by Underwriters Laboratories. Canadian standards C22.2 No. 24-93
General Instructions: Refer to F-25911


Main menu 2