Jump to Navigation

Schneider Electric TC-1xx Series, TC-11xx Series, TF-1111 Series Two-Position Electric Duplex Room Thermostats

Two-Position Electric Duplex Room Thermostats
TC-1xx Series, TC-11xx Series, TF-1111 Series

These thermostats provide on-off control of heating/cooling systems.

 

 

• Separate units for °C and °F.
• All units except TC-114. - Parallel heat and/or cooling anticipation capability. - Dial stop pins to limit range. - Lock cover screw/sets available. - Agency approval. - Switch bases AT-602 and AT-603 available for custom applications.
• TC-18x and TC-19x. - Fan switch option standard.

 

 

 

Select a link under the "item" tab below to order.

Cat #Setpoint Dial RangeDifferential F Degrees (C Degrees)Electrical Switch Refer to Electrical Ratings Table
TC-11450 to 90°F (10 to 32°C) Dual markedHeat, 2 (1.1) Cool, 4 (1.7°)SPDT snap action
TC-186ª55 to 85°FHeat, 2 Neutral, 2 Cool, 2SPDT zero energy band (neutral center)
TC-187ª55 to 85°FHeat, 2 Neutral, 2 Cool, 2SPDT zero energy band (neutral center)
TC-188ª55 to 85°FHeat, 2 Neutral, 2 Cool, 2SPDT zero energy band (neutral center)
TC-187-11613 to 29°CHeat, (1.1) Neutral, (1.1) Cool, (1.1)SPDT zero energy band (neutral center)
TC-188-11613 to 29°CHeat, (1.1) Neutral, (1.1) Cool, (1.1)SPDT zero energy band (neutral center)
TC-195ª55 to 85°F (13 to 29°C)1.5 (0.8)SPDT snap action
TC-199ª55 to 85°F (13 to 29°C)Heat, 2 (1.1) Cool, 2 (1.1) Neutral, 2 (1.1)SPDT zero energy band (neutral center)
TC-110155 to 85°F2 (1.1)SPDT snap action
TC-1101-11613 to 29°C1°C° (1.8°F°)SPDT snap action
TC-1101-500ª55 to 85°F2 (1.1)SPDT snap action
TC-110245 to 75°F2 (1.1)SPDT snap action
TC-1102-1167 to 23°C1°C° (1.8°F°)SPDT snap action
TC-1102-500ª45 to 75°F2 (1.1)SPDT snap action
TC-1102-602b45 to 75°F2 (1.1)SPDT snap action
TC-110375 to 105°F2 (1.1)SPDT snap action
TC-1103-11624 to 40°C1°C° (1.8°F°)SPDT snap action
TC-1103-500 ª75 to 105°F2 (1.1)SPDT snap action
TC-119155 to 85°FHeat, 2 (1.1) Cool, 2 (1.1) Neutral, 2 (1.1)SPDT (neutral center)
TC-1191-11613 to 29°CHeat, 2 (1.1) Cool, 2 (1.1) Neutral, 2 (1.1)SPDT (neutral center)
TC-1191-500 ª55 to 85°FHeat, 2 (1.1) Cool, 2 (1.1) Neutral, 2 (1.1)SPDT (neutral center)
TC-1191-602 b55 to 85°FHeat, 2 (1.1) Cool, 2 (1.1) Neutral, 2 (1.1)SPDT (neutral center)
TF-111155 to 85°F4 (2.2)SPDT floating off 0.160 FLA @ 24 Vac
TF-1111-11613 to 29°C(2)SPDT floating off 0.160 FLA @ 24 Vac
Anticipators: Thermostats mounted on concrete walls or surfaces that change temperature slowly, have reduced response to changes in air temperature. Response is further delayed by guards that restrict air flow to the thermostat. Anticipators are required (parallel for cooling, series or parallel for heating) for any of these conditions and in spaces intended for continuous occupancy; i.e., hotel guest rooms and offices
Anticipation:
TC-18x Series: TF-1111 Series
TF-1111 Series: Heating and cooling; factory-installed resistors are sized for 0.16 FLA @ 24 Vac maximum
Fan Switch:
TC-18x Series: Marking: Low-Off-Med-High
TC-19x Series: Marking: Off-Lo-Hi
Construction: Integral two-pole three-position
Sensing Element: Bimetal
Mounting: Flush or 2 x 4 wall box
Locations: NEMA Type 1
General Instructions: TC-18x: Refer to F-20044
TC-19x: Refer to F-15688
TC-110x: Refer to F-18785
TC-119x: Refer to F-18781
TF-1111-xxx: Refer to F-21666