Fixed Trip Point (H300... H900) Current Switches: Fixed Trip Point

Current Switches: Fixed Trip Point
Fixed Trip Point (H300... H900)

Hawkeye x00 go/no go current switches provide a cost-effective solution for monitoring status on unit vents, exhaust fans, recirculation pumps, and other fixed loads where belt loss is not a concern. Veris has applied new technology to the H300, H600, and H800 models to achieve impressive improvement in turn-on levels. The Hawkeye H300 and H600 now have the lowest turn-on current in the industry at a mere 150mA!

On/off status for direct-drive fans, pumps, and process motors
• More reliable for status than relays across auxiliary contacts
• Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other fixed loads
• Great for lighting status–less expensive than 277V relays
• Low 0.15A turn-on (H300 and H600)...ideal for small exhaust fans (not intended to detect belt loss)
• Removable mounting bracket provides installation flexibility
• Bracket on H900 can be installed in three different configurations Monitor status of fans, pumps, motors & other electrical loads
• Split-core H300, H600, and H900 for fast retrofit installation
• Mini solid-core H800 and micro split-core H300 fit in tight enclosures...saves valuable panel space
• 100% solid-state, no moving parts to fail
• Polarity insensitive output
• 5-year limited warranty

Select a link under the "item" tab below to order.

Cat #TRIP POINTAMPERAGE RANGEStatus Output (max.)HousingRoHS
H3000.15A or less0.15 - 60AN.O. 1.0A@30VAC/DCSplit-core
H6000.15A or less0.15 - 200AN.O. 1.0A@30VAC/DCSplit-core
H8000.25A or less0.25 -200AN.O. 1.0A@30VAC/DCSolid-core
H800NC0.5A or less0.5 - 200AN.C. 0.1A@30VDCSolid-core
H800HV0.75A or less0.75 - 200AN.O. 0.5A@250VAC/DCSolid-core
H9001.5A or less1.5 - 200AN.O. 1.0A@30VAC/DCSplit-core
Sensor Power (N.O. Models): Induced from monitored current
Insulation Class: 600VAC RMS (UL), 300VAC RMS (CE)
Temperature Range: H800, H800NC, H300, H900: -15° to 60°C (5° to 140°F)
H600: -15° to 40°C (5° to 104°F) (to 200A); -15° to 60°C (5° to 140°F) (to 150A)
H800HV: -40° to 50°C (-40° to 122°F) (to 200A); -40° to 75°C (-40° to 167°F) (to 100A, & 0.25A output)
Humidity Range: 10-90% RH, non-condensing
Sensor Power (N.C. Models: 10-90% RH, non-condensing
Sensor Power (N.C. Models): 5-30VDC, permanently connected
Off State Leakage (N.C. Models): 34μA@5VDC, 200μA@30VDC
On State Voltage Drop (N.C. Models): 1.9VDC (max.) @0.1A
Terminal Block Maximum Wire Size: 14 AWG (16 AWG for H300)
Terminal Block Torque (nominal): 4 in-lbs (7 in-lbs for H300)
Agency Approvals: UL 508 open device listing
CE:EN61010-1:2001-02, CAT III, deg. 2, basic insulation