Honeywell DR4300 10” Circular Chart Recorders

10” Circular Chart Recorders
DR4300

The DR4300 Circular Chart Recorder provides one of the most cost-effective solutions for dependable pen drawn analog traces on a 10-inch (250 mm) chart.

It is easy to set up and configure to match a wide range of applications such as food processing, environmental monitoring, machine monitoring, flow, water and waste monitoring, for use on furnaces and ovens, packaging machines, and numerous other processes.

The DR4300 Recorder gives you the flexibility to tailor the recorder to match any application, from basic recording to actually doing the process control, by choosing the options that are required to accomplish your application needs. Both one- and two-pen models accept inputs from any one of a variety of sensors or transmitters within the configurable range limits. The DR4300 can be specified with a variety of options such as one or two digital controllers, a vacuum fluorescent display for viewing the process variable or configuration using English language prompts. You can also select Modbus™ communications, or choose a number of software options such as a timer function, setpoint programming, or advanced fuzzy tuning/PID control.

• Charts—Over 200 preprinted charts available to meet specific recording needs.
• Ink Cartridge—Disposable fiber-tip ink cartridge for dependable recording with minimum maintenance.
• Universal Power—Eliminates the concern with matching the local power requirements.
• Universal Inputs—Accepts 10 thermocouple types, RTDs, mA, mV or voltage inputs through simple configuration.
• Thermocouple Failsafe—Configurable upscale or down-scale burnout.
• Manual/Automatic Modes—Bumpless, balanceless transfer between control modes on advanced recorders.
• User Configurable—Allows you to set up or alter operating parameters to fit your requirements. Easily set DIP switch configuration on basic recorder.
• A Vacuum Fluorescent Display/ Keypad with English language prompts is available for more advanced recorder set up and monitoring.
• Optional Outputs—Choose from Alarm, On-Off Control, Limit Control, or versatile PID digital controller.
• Accutune II™—Provides a new, truly plug and play tuning algorithm, which will, at the touch of a button or through a digital input, accurately identify and tune any process including those with deadtime and integrating processes. This speeds up and simplifies start-up plus allows retuning at any setpoint.
• Fuzzy Logic—This new feature uses fuzzy logic to suppress process variable overshoot due to SP changes or externally induced process disturbances. It operates independently from Accutune tuning. It does not change the PID constants, but temporarily modifies the internal controller response to suppress overshoot. This allows more aggressive tuning to co-exist with smooth PV response. It can be enabled or disabled depending on the application or the control criteria.
• Individual Pen Options—Include Totalization, a Timer function, Digital Inputs, Auxiliary Output, and Setpoint Programming allowing the most flexibility to meet the application need.
• Quality/Support—The DR4300 is backed up by a toll-free phone number for technical assistance.
• CE Mark—Conformity with 73/23/EEC, Low Voltage Directive and 89/336/EEC, the EMC Directive.

Select a link under the "item" tab below to order.

Table 1Table 2Table 3Table 4Table 5Table 6Table 7Table 8Table 9Table 10Table 11Table 12Table 13Table 14
XXXXXXXXXXXXXXXXXXXXX
Table 1KEY NUMBER
DR4301One Pen Recorder
DR4302Two Pen Recorder
DR4311One Pen Recorder
DR4312Two Pen Recorder
DR4321One Pen Recorder
DR4322Two Pen Recorder
DR4331One Pen Recorder
DR4332Two Pen Recorder
Table 2Product Configuration
0Standard Factory Configuration
1Configuration for non-standard range settings
2Configuration to customer’s specific data
Table 3PEN 1 Options
00No Totalizer Function
T0No Totalizer Function
00No Digital Inputs
D0Digital Inputs
Table 4PEN 2 Options
00No Digital Inputs
D0Digital Inputs
00No Totalizer Function
T0Totalizer
Table 5Approvals
0No Approvals
UUL Listing
CCSA Certification
BUL and CSA Approval
Table 6Certificates
0No Certificates
1Certificate of Conformance (F3391)
2Certificate of Calibration (F3399)
3Certificate of Conformance & Calibration
Table 7Documentation
0Product Information on CD
EHard Copy Product Manual
Table 8Pen One
0None
22 Outputs (Alarm/On-Off Control)
31 PID Control with Accutune
41 PID Control/Setpoint Program/Timer
52 Outputs (Alarm1/Timer)
A4-20 mA Retransmission Output
FFM Approved Limit Control
GFM Approved Limit Control/Timer Output
Table 9Pen Two
0None
22 Outputs (Alarm/On-Off Control)
31 PID Control
41 PID Control/Setpoint Program/Timer
52 Outputs (Alarm1/Timer)
A4-20 mA Retransmission Output
FFM Approved Limit Control
GFM Approved Limit Control/Timer Output
Table 10Output Type Pen One
0None
EElectromechanical Relay
SSolid State Relay
TOpen Collector
Table 11Output Type Pen Two
0None
EElectromechanical Relay
SSolid State Relay
TOpen Collector
Table 12Door Options
GGray Door
BBlue Door
HGray Door with Key Pad
CBlue Door with Key Pad
KBlack Door
LBlack Door with Key Pad
RHeavy Duty SST Door
0None
AKeyed Latch
BKeyed Latch/Chart Plate Seal
EStandard Latch/Chart Plate Seal
MDoor Lock
KDoor Lock / Chart Plate Seal
Table 13Instrument Power/Transmitter Power
1Universal Power
3Universal Power +24VDC Transmitter Power
Table 14Communications
0None
CRS 485 Modbus RTU Communication
Minimum Input Span: Range is fully configurable within span limitation of the sensing element.
Input Impedance: mA dc: 250 ohms
Vdc: 200 K ohms
RTD: 13.3 K ohms
All Others: 10 Megohms
Input Filter: Without Display: Analog with time constant of 3 seconds and digital with time constant of 1 second.
With Display: Analog with time constant of 3 seconds and digital adjustable 0 seconds to 120 seconds.
Digital Displays (Optional): Vacuum fluorescent, alphanumeric
An upper four-digit display dedicated to the process variable or setpoint.
Alternate information displayed during configuration.
A six-digit lower display shows key selected operating parameters. Also provides guidance during configuration.
Modes of Operation: Manual
Automatic with local set point
Indicators: Channel PV display (INP 1 or 2)
Controller output (OUT 1 or 2)
Temperature unit (F or C)
Controller's mode (A or M)
Active Setpoint [L = SP1 active; R = SP2(S2) active]
Case: Molded, foamed-Noryl* with gasketed door to meet NEMA 3 enclosure requirements.
*Registered Trademark — General Electric Co.
Pen: Disposable fiber-tip ink cartridge, line length per cartridge more than 1000 ft (305 m)
One Pen: Purple
Two Pen: Purple (pen one) and red (pen two)
NOTE: Only pen 1 (purple) is referenced to the chart time line.
Chart: 10.24-inch (260 mm) diameter chart with standard preprinted markings and a calibrated width of 4 inches (100 mm).
Wiring Connections: Two piece wiring connectors inside case.
Color: Case: Black
Door: Gray (standard); Caribbean blue (optional)
Window: Acrylic
Approval Bodies: CE Mark, UL, CSA, FM Approved Limit Controller
Weight: 12 lb. (5.4 kg)
Mounting: Panel, surface, or 2-inch pipe mounting
Tuning: PID tuning parameters of Gain or PB, Rate, Reset.
Chart: For Basic Recorder chart speeds set as part of configuration for 8 hours, 12 hours, 24 hours or 7 days; with Display/Keypad speeds selectable from 1 hour to 744 hours.
Sensor Burnout: Selectable for None, Up, or Down.
Alarms: Type: Based on PV or deviation, high or low state Hysteresis: 0 % to 100 % of input span
Transmitter Power: 24 Vdc with adjustment of ± 6 % (22.6 to 25.4) 100 mA maximum output