Johnson Controls FX16 Master Controller

Master Controller
FX16

The FX16 Master Controller is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications.

The FX16 supports 27 physical inputs and outputs, including a wide range of sensors and actuating devices. You can add up to 72 physical inputs and outputs to the controller using I/O extension modules. The FX16 can manage a distributed control application with up to 16 slave FX controllers. The FX16 can also monitor and control a number of N2 Open compatible devices through its gateway feature.

Multiple user interface options allow you to monitor and/or adjust the FX16s operation, either locally or remotely. The FX16 can be fitted with an N2 Open, LONWORKS®, or BACnet® communication card to integrate the controller into a compatible Building Automation System (BAS). Alternatively, the FX16 can be fitted with an RS-232C serial communication card to transmit event notification messages via e-mail or Short Messaging Service (SMS) through a Global System for Mobile Communications (GSM) modem. With its onboard Web server, you can browse and make adjustments to the application from a remote location.

Using the FX Tools Pro software package, you can program the FX16 Master Controller to operate a wide range of commercial HVAC and refrigeration equipment such as chillers, air handling units (AHUs), and close control units, as well as small distributed control systems with terminal units. Refer to the FX16 Master Controller Product Bulletin (LIT-12011084) for important product application information.

• optional integral or remote User Interfaces (UIs)
• distributed control application
• embedded Web server
• communication services
• network communications options – N2 Open, LONWORKS, or BACnet protocol
• freely programmable or configurable using FX Tools Pro
• onboard trend and event logging
• analog input types selected in software

Select a link under the "item" tab below to order.

Cat #DescriptionsType
LP-FX16X00-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), no communication cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X01-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), N2 Open cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X02-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), LON cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X03-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), RS-232C cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X04-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), BACnet cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X50-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), no communication cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X51-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), N2 Open cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X52-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), LON cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X53-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), RS-232C cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X54-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (9 relays), BACnet cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X10-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), no communication cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X11-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), N2 Open cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X13-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), RS-232C cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X14-000CFX16, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), BACnet cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X60-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), no communication cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 1 of 2)
LP-FX16X61-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), N2 Open cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 2 of 2)
LP-FX16X62-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), LON cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 2 of 2)
LP-FX16X63-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), RS-232C cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 2 of 2)
LP-FX16X64-000CFX16, with display, 6 AIs, 8 DIs, 4 AOs, 9 DOs (4 relays, 5 triacs), BACnet cardFX16 Master Controller - Extended Temperature Range Controllers (Rev. A and B) Ordering Information (Part 2 of 2)
LP-NET151-010CN2 Open communication card for LP-FX16D and LP-FX16X (not Rev. A or B) controllersFX16 Communications Cards (for Upgrade or Replacement) Ordering Information
LP-NET161-000CN2 Open communication card for LP-FX16X Rev. A controllersFX16 Communications Cards (for Upgrade or Replacement) Ordering Information
LP-NET152-010CLON communication card for LP-FX16 controllersFX16 Communications Cards (for Upgrade or Replacement) Ordering Information
LP-NET163-000CRS-232C communication card for LP-FX16 controllersFX16 Communications Cards (for Upgrade or Replacement) Ordering Information
LP-NET164-000CBACnet communication card for LP-FX16X Rev. B controllersFX16 Communications Cards (for Upgrade or Replacement) Ordering Information
LP-DIS60P20-0CMedium User Interface for FX16 (non-isolated version); can be mounted up to 3 m (9.8 ft) from the FX16 and includes panel mounting hardware.User Interfaces Ordering Information
LP-DIS60P21-0CMedium User Interface for FX16 (isolated version); can be mounted up to 300 m (1,000 ft) from the FX16 and includes panel and wall mounting hardware.User Interfaces Ordering Information
LP-XM07X01-000CFX I/O Module 5 UI, 4 BI, 3 AO, 6 Relay DO, 24 VAC power supplyXM07 I/O Modules - 24 VAC Power Supply
LP-XM07X11-000CFX I/O Module 5 UI, 4 BI, 3 AO, 2 Triac DO, 4 Relay DO, 24 VAC power supplyXM07 I/O Modules - 24 VAC Power Supply
LP-XM07X51-000CFX I/O Module 5 UI, 4 BI, 3 AO, 6 Relay DO, 24 VAC power supply Manual Overrides for 2 AO and 4 Relay DOXM07 I/O Modules - 24 VAC Power Supply
LP-XM07X61-000CFX I/O Module 5 UI, 4 BI, 3 AO, 2 Triac DO, 4 Relay DO, 24 VAC power supply Manual Overrides for 2 AO, 2 Triac DO and 2 Relay DOXM07 I/O Modules - 24 VAC Power Supply
LP-XM14X01-000CFX I/O Module 6 UI, 12 BI, 4 AO, 9 Relay DO, 24 VAC power supplyXM14 I/O Modules - 24 VAC Power Supply
LP-XM14X11-000CFX Module 6 UI, 12 BI, 4 AO, 4 Triac DO, 5 Relay DO, 24 VAC power supplyXM14 I/O Modules - 24 VAC Power Supply
LP-XM14X51-000CFX I/O Module 6 UI, 12 BI, 4 AO, 9 Relay DO, 24 VAC power supply Manual Overrides for 3 AO and 7 Relay DOXM14 I/O Modules - 24 VAC Power Supply
LP-XM14X61-000CFX I/O Module 6 UI, 12 BI, 4 AO, 4 Triac DO, 5 Relay DO, 24 VAC power supply Manual Overrides for 3 AO, 2 Triac DO and 5 Relay DOXM14 I/O Modules - 24 VAC Power Supply
LP-XT91D00-000CI/O Extension ModuleExpansion Input/Output (I/O) Modules (System 91 Series) Ordering Information (Part 1 of 2)
LP-XP91D05-000CI/O Expansion Module - 8 DIExpansion Input/Output (I/O) Modules (System 91 Series) Ordering Information (Part 2 of 2)
LP-XP91D07-000CI/O Expansion Module - 4 relays, 24 V 3 A (North America Only)Expansion Input/Output (I/O) Modules (System 91 Series) Ordering Information (Part 2 of 2)
LP-FXTPRO-0FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, and FX CommPro BACnet) - New UserSoftware Tools Ordering Information
LP-FXTPRO-6FX Tools Pro CD-ROM (FX Builder, FX CommPro N2, FX CommPro LON, and FX CommPro BACnet) - UpgradeSoftware Tools Ordering Information
Product Codes FX16D Master Controller
FX16X Master Controller Extended Temperature Range
Power Supply Requirements 24 VAC ±15%, 50/60 Hz - Class 2 Power Supply – Safety Extra-Low Voltage (SELV) in Europe
Power Consumption 15 VA at max load
Internal Fuse 2 A, 250 V
Protection Class IP 20 CEI/EN60529
Ambient Operating Conditions FX16D: -20 to 50°C (-4 to 122°F),10 to 95% RH (noncondensing)
FX16X Extended Temperature Range: -40 to 60°C (-40 to 140°F),10 to 95% RH (noncondensing) (Integral Display may not operate below -20°C [-4°F])
Ambient Storage Conditions -40 to 70°C (-40 to 158°F), 10 to 95% RH (noncondensing)
Dimensions (H x W x D) 142 (including terminals) x 215 x 49 mm (66 mm with integral display)
5.59 (including terminals) x 8.46 x 1.93 in. (2.6 in. with integral display)
Weight (in Package) 0.95 kg (2.1 lb)
Real-Time Clock Accuracy: Better than ± 200 ms per day at constant ambient temperature of 25°C
Backup: Minimum 3 years without power at 25°C
Connection Terminals for Inputs, Outputs,
and Power Supply
Screw terminals for max 2 x 1.5 mm2 (16 AWG) wires
N2 Open and BACnet MS/TP Bus Connection Terminals Screw terminals, cable size 0.5 mm to 1.5 mm2, 24 to 16 AWG, Belden® cable, 4-core twisted pair with shield
LON Network Connection Terminals  Screw terminals, cable size 0.5 mm to 1.5 mm2, 24 to 16 AWG, Belden cable, 2-core twisted pair with shield
Connection for Extension Bus and Remote Display Screw terminals, cable size 0.5 mm to 1.5 mm2, 24 to 16 AWG, Belden cable, 4-core twisted pair with shield
BACnet® Compliance BACnet Testing Laboratories™ (BTL) Listing
BACnet Interoperability Building Blocks (BIBBs): BACnet Advanced Application Controller (B-AAC)
Protocol Implementation Conformance Statement (PICS) available on request
CE and UL Compliance Europe – 89/336/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-1
– 72/23/EEC, Low Voltage Directive: EN 60730
Canada – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
– Industry Canada, ICES-003
United States – UL Listed (PAZX), UL 916, Energy Management Equipment
– FCC compliant to CFR 47, Part 15, Subpart B, Class A

 

Ordering Information- North America
Ordering Information- Europe