Jump to Navigation

Johnson Controls FX15 Field Controller

Field Controller
FX15

The FX15 Field Controller (FX15 Classic) is a high performance field controller in the Facility Explorer system specifically designed for commercial Heating, Ventilating, and Air Conditioning (HVAC) and refrigeration applications such as chillers and rooftops, indoor packaged air conditioning units, Air Handling Units (AHUs), and close control units.

The FX15 has 27 physical inputs and outputs and supports a wide range of temperature sensors and actuating devices. Up to 64 additional physical inputs and outputs may be achieved by adding the XT/XP expansion modules on the Local N2 Open bus.

The FX15 is fully programmable or configurable, using the FX Tools software package, for a wide range of commercial HVAC and refrigeration applications. The FX15 controller can be fitted with an optional communication card for integration into an N2 Open or LONWORKS® compatible Building Automation System.

• Modular Communication Card Options : Provide cost-effective method for either stand-alone or networked capabilities.
• Onboard Real-Time Clock : Allows real-time scheduling of control activities.
• Freely Programmable or Configurable Using FX Tools Software Package : Adapts to a wide range of HVAC or refrigeration control applications using the extensive programming features of the FX Tools software package.
• Software Selectable Analog Inputs : Allow choice of temperature sensor according to the control range and application.
• User Interfaces, Integrated or Remote : Provide clear data presentation in numerical and text format on Liquid Crystal Display (LCD) 4 x 20 character display to manage the controlled system.

Select a link under the "item" tab below to order.

Cat #DescriptionsType
LP-FX15D10-000CFX15: Digital Outputs: 4 Relays and 5 TriacsStandard Temperature Range Controllers Ordering Information
LP-FX15D11-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes N2 Open Card.Standard Temperature Range Controllers Ordering Information
LP-FX15D12-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes LONWORKS CardStandard Temperature Range Controllers Ordering Information
LP-FX15D60-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes Integrated MUI.Standard Temperature Range Controllers Ordering Information
LP-FX15D61-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes N2 Open Card and Integrated MUI.Standard Temperature Range Controllers Ordering Information
LP-FX15D62-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes LONWORKS Card and Integrated MUI.Standard Temperature Range Controllers Ordering Information
LP-FX15D20-000CFX15: Digital Outputs: 9 RelaysStandard Temperature Range Controllers Ordering Information
LP-FX15D21-000CFX15: Digital Outputs: 9 Relays. Includes N2 Open Card.Standard Temperature Range Controllers Ordering Information
LP-FX15D22-000CFX15: Digital Outputs: 9 Relays. Includes LONWORKS Card.Standard Temperature Range Controllers Ordering Information
LP-FX15D70-000CFX15: Digital Outputs: 9 Relays. Includes Integrated MUI.Standard Temperature Range Controllers Ordering Information
LP-FX15D71-000CFX15: Digital Outputs: 9 Relays. Includes N2 Open Card and Integrated MUI.Standard Temperature Range Controllers Ordering Information
LP-FX15D72-000CFX15: Digital Outputs: 9 Relays. Includes LONWORKS Card and Integrated MUI.Standard Temperature Range Controllers Ordering Information
LP-FX15X10-000CFX15: Digital Outputs: 4 Relays and 5 TriacsExtended Temperature Range Controllers Ordering Information
LP-FX15X11-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes N2 Open Card.Extended Temperature Range Controllers Ordering Information
LP-FX15X12-000CFX15: Digital Outputs: 4 Relays and 5 Triacs. Includes LONWORKS Card.Extended Temperature Range Controllers Ordering Information
LP-FX15X20-000CFX15: Digital Outputs: 9 RelaysExtended Temperature Range Controllers Ordering Information
LP-FX15X21-000CFX15: Digital Outputs: 9 Relays. Includes N2 Open Card.Extended Temperature Range Controllers Ordering Information
LP-FX15X22-000CFX15: Digital Outputs: 9 Relays. Includes LONWORKS Card.Extended Temperature Range Controllers Ordering Information
LP-NET151-010CN2 Open Communication CardCommunications Cards Ordering Information
LP-NET152-010CLONWORKS Communication CardCommunications Cards Ordering Information
LP-KIT007-000CLink Interface cable (3 m/9.8 ft) for the connection of the FX15 to the MUI/LUI user interfacesAccessories Ordering Information
LP-KIT007-020CBag of replacement communication wiring connectorsAccessories Ordering Information
DT-9100-8902LUI Wall Mounting KitAccessories Ordering Information
NP-PWR1209LUI Power Adapter (120 VAC/12 VDC)Accessories Ordering Information
DT-9100-8901LUI Power Adapter (230 VAC/12 VDC)Accessories Ordering Information
LP-KIT015-000CKit of Female Screw ConnectorsAccessories Ordering Information
LP-KIT100-000CFX Programming KeyAccessories Ordering Information
LP-DIS65P10-0CLarge User InterfaceUser Interfaces Ordering Information
LP-DIS60P10-0CMedium User Interface (Local Mount)User Interfaces Ordering Information
LP-DIS60P11-0CMedium User Interface (Remote Mount)User Interfaces Ordering Information
LP-DIS60U10-CMedium User Interface (Integral Mount)User Interfaces Ordering Information
LP-XT91D00-000CExtension ModuleExpansion I/O Modules Ordering Information
LP-FXTPRO-0FX Tools Pro CD (Includes the FX Builder, FX CommPro N2, and LON Software) - New UserSoftware Tools Ordering Information
LP-FXTPRO-6FX Tools Pro CD (Includes the FX Builder, FX CommPro N2, and LON Software) - Upgrade 6 FX15 Field Controller Product BulletinSoftware Tools Ordering Information
Product Codes LP-FX15Dxx-000C
Power Supply Requirements 24 VAC ±15%, 50/60 Hz - Class 2 Power Supply – SELV in Europe
Power Consumption 15 VA at max load
Protection Class IP20 controller
IP40 integrated MUI
Ambient Operating Conditions STD controller: -20°C (-4°F) to +50°C (122°F), 10 to 95% RH (noncondensing)
Extended range controller: -40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing)
Ambient Storage Conditions -20°C (-4°F) to 70°C (158°F), 10 to 95% RH (noncondensing)
Dimensions (H x W x D) 142 mm (5.6 in.) x 215mm (8.5 in.) x 49 mm (1.9 in.)
Weight (with Package) 0.74 kg (1.6 lb)
Connection Terminals for Signals and Power Supply Screw terminals for max 1 x 1.5 mm2 (AWG16) wires, included in the package.
LON/N2 Open Bus Connection Terminals Screw terminals, cable size 0.2 to 1.5 mm2, AWG24 to AWG16, included in the package. BeldenR cable, 2-core twisted pair with shield. 0.8 mm (AWG20)
Connection Terminals for Extension Bus and Remote Display Screw terminals, cable size 0.2 to 1.5 mm2, AWG24 to AWG16, included in the package.
Single Cable Lengths
Digital Inputs DI1 - DI8
Analog Inputs AI1 - AI6
Triac outputs (when present)
Analog Outputs AO1 - AO4
Remote Display
Extension Modules
Display and Extensions Cable Type
Max. 100 m (328 ft) with wire ≥ 0.6 mm (AWG22)
Max. 100 m (328 ft) with wire ≥ 0.6 mm (AWG22)
Max. 100 m (328 ft) with wire = 1.5 mm2 (AWG16)
Max. 100 m (328 ft) with wire + 1.5 mm2 (AWG16)
Max. 3 m (10 ft) if display is powered by controller. Max. 1 km (0.6 miles) if display independently powered.
Max. 1 km (0.6 miles)
Belden 4-core, twisted pair, shielded, ≥ 0.8 mm (AWG20)
Compliance Europe – 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-2
– 2006/95/EEC, Low Voltage Directive: EN 60730
Canada – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
– UL Recognized (XAPX8), CAN/CSA C22.2 No. 24, Temperature Indicating and Regulating Equipment
– Industry Canada, ICES-003
United States – UL Listed (PAZX), UL 916, Energy Management Equipment
– UL Recognized (XAPX2), UL 873, Temperature Indicating and Regulating Equipment
– FCC compliant to CFR 47, Part 15, Subpart B, Class A


Main menu 2