Jump to Navigation

Johnson Controls FX14 Field Controller

Field Controller
FX14

The FX14 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning, and Refrigeration (HVACR) applications.

The FX14 supports 29 physical inputs and outputs including a wide range of sensors and actuating devices. The FX14 includes an onboard real-time clock to support the start-stop scheduling of equipment, real-time based control sequences, and the time stamping of events and trend records.

The FX14 can be fitted with an N2 Open, LONWORKS®, or BACnet® communication card to integrate the controller into a compatible Building Automation System (BAS). Alternatively, the FX14 can be fitted with an RS-232C serial communication card to transmit event notification messages via Short Messaging Service (SMS) through a Global System for Mobile (GSM) modem.

Using the FX Tools software package, you can program the FX14 field controller to operate a wide variety of commercial HVACR equipment, including multi-compressor and scroll compressors, close control units, unit ventilators and packaged rooftop units.

Refer to the FX14 Field Controller Product Bulletin (LIT-12011163) for important product application information.

• freely programmable controller
• network communication card options - N2 Open, LONWORKS, and BACnet Protocols
• remote communication services
• choice of user interfaces: integral or remote
• onboard real-time clock
• selectable analog input types in software
• analog outputs with Pulse Width Modulation (PWM) option
• models with various output configurations of solid-state triacs and line voltage relays
• Network Room Module (NRM)

Select a link under the "item" tab below to order.

Cat #DescriptionsType
LP-FX14D10-000CFX14: 6 Analog Inputs (AIs), 12 Digital (Binary) Inputs (DIs), 2 Analog Outputs (AOs) (0-10 V or PWM), and 9 Digital (Binary) Outputs (DOs) (5 Relays and 4 Triacs), no communication cardFX14 Controllers Ordering Information
LP-FX14D11-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), N2 Open cardFX14 Controllers Ordering Information
LP-FX14D12-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), N2 Open cardFX14 Controllers Ordering Information
LP-FX14D14-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), BACnet cardFX14 Controllers Ordering Information
LP-FX14D60-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface, no communciation cardFX14 Controllers Ordering Information
LP-FX14D61-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and N2 Open cardFX14 Controllers Ordering Information
LP-FX14D62-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and LONWORKS cardFX14 Controllers Ordering Information
LP-FX14D63-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and RS-232C cardFX14 Controllers Ordering Information
LP-FX14D64-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (5 Relays and 4 Triacs), Integral User Interface and BACnet cardFX14 Controllers Ordering Information
LP-FX14D20-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), no communciation cardFX14 Controllers Ordering Information
LP-FX14D21-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), N2 Open cardFX14 Controllers Ordering Information
LP-FX14D22-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), N2 Open cardFX14 Controllers Ordering Information
LP-FX14D23-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), RS-232C cardFX14 Controllers Ordering Information
LP-FX14D70-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), RS-232C cardFX14 Controllers Ordering Information
LP-FX14D71-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and N2 Open cardFX14 Controllers Ordering Information
LP-FX14D72-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and LONWORKS cardFX14 Controllers Ordering Information
LP-FX14D73-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and RS-232C cardFX14 Controllers Ordering Information
LP-FX14D74-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), Integral User Interface and BACnet cardFX14 Controllers Ordering Information
LP-FX14D24-000CFX14: 6 AIs, 12 DIs, 2 AOs (0-10 V or PWM), and 9 DOs (9 Relays), BACnet cardFX14 Controllers Ordering FX14 Controllers Ordering Information
LP-NET151-010CN2 Open communication card for FX14 Rev. AFX14 Communications Cards Ordering Information
LP-NET142-000CLONWORKS communication card for FX14 Rev. AFX14 Communications Cards Ordering Information
LP-NET163-000CRS-232C communication card for FX14 Rev. AFX14 Communications Cards Ordering Information
LP-NET164-000CBACnet communication card for FX14 Rev. B onlyFX14 Communications Cards Ordering Information
TM-2140-0000Room Command Module, temperature sensor onlyTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2150-0000Room Command Module, occupancy button and LEDTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2160-0000Room Command Module, 12-28°C setpoint dial, occupancy button and LEDTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2160-0002Room Command Module, 12-28°C setpoint dial, occupancy button and LED, fan speed overrideTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2160-0005Room Command Module, ± setpoint dial, occupancy button and LEDTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2160-0007Room Command Module, ± setpoint dial, occupancy button and LED, fan speed overrideTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2190-0000Room Command Module, 12-28°C setpoint dialTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2190-0005Room Command Module, ± setpoint dialTM Series Room Command Modules (80 x 80 mm [3.15 x 3.15 in.], °C, European Models)
TM-2141-0000Room Command Module, temperature sensor onlyTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2151-0000Room Command Module, occupancy button and LEDTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2161-0000Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LEDTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2161-0002Room Command Module, 54-82°F/12-28°C setpoint dial, occupancy button and LED, fan speed overrideTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2161-0005Room Command Module, ± setpoint dial, occupancy button and LEDTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2161-0007Room Command Module, ± setpoint dial, occupancy button and LED, fan speed overrideTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2191-0000Room Command Module, 54-82°F/12-28°C setpoint dialTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
TM-2191-0005Room Command Module, ± setpoint dialTM Series Room Command Modules Ordering Information (120 x 80 mm [4.72 x 3.15 in.], °F/°C, North American Models)
LP-DIS60P20-0CMedium User Interface display (non-isolated version); can be mounted up to 3 m (9.8 ft) from the FX14 and includes panel mounting hardware.Medium User Interfaces Ordering Information
LP-DIS60P21-0CMedium User Interface display (isolated version); can be mounted up to 300 m (984 ft) from the FX14 and includes panel and wall mounting hardware.Medium User Interfaces Ordering Information
LP-FXTPRO-0FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) – New UserProgramming/Commissioning Tools Ordering Information
LP-FXTPRO-6FX Tools Pro CD (FX Builder, FX CommPro N2, LON, BACnet) - UpgradeProgramming/Commissioning Tools Ordering Information
LP-KIT200-000CN2 Commissioning Adapter: Includes port powered RS-232 to RS-485 converter and wiring harness with mating connectors for FX Field Controller supervisory link interfaceProgramming/Commissioning Tools Ordering Information
LP-KIT204-000CBACnet Commissioning Adapter: Includes BACnet Internet Protocol (IP) to MS/TP adapter, Ethernet cable, and Universal Serial Bus (USB) cable (USB port required for powering the adapter).Programming/Commissioning Tools Ordering Information
LN-75010LONWORKS Commissioning Adapter: Includes USB to LONWORKS TP/FT-10 Network InterfaceProgramming/Commissioning Tools Ordering Information
LP-KIT100-000CFX Programming KeyProgramming/Commissioning Tools Ordering Information
DT-9100-8901Power Supply Adapter for Programming Key: 230 VAC/12 VDC (Europe Only)Programming/Commissioning Tools Ordering Information
Product Codes LP-FX14Dxx-xxx
Power Supply Requirements 24 VAC ±15%, 50/60 Hz – Safety Extra-Low Voltage (SELV) in Europe - Class 2 North America
Power Consumption 19.5 VA at max. load
Housing Material ABS + polycarbonate, self-extinguishing: UL 94-5VB flammability rating
Protection Class IP20 CEI/EN60529
Ambient Operating Conditions -40°C (-40°F) to 60°C (140°F), 10 to 95% RH (noncondensing)
Integral user interface does not operate below -20°C (-4°F).
Ambient Storage Conditions -40°C (-40°F) to 70°C (158°F), 10 to 95% RH (noncondensing)
Weight (with Package) 0.74 kg (1.6 lb)
Real-Time Clock Accuracy: better than ±200 ms per day at constant ambient temperature of 25°C
Back up: minimum 10 days without power at 25°C
Integrated LCD Display Numeric Resolution -999 to 999 or -99.9 to 99.9
Connection Terminals for AIs, DOs and Power Supply Screw terminals for max. 2 x 1.5 mm2 (16 AWG) wires, included in the package.
Connection Terminals for AOs, DIs and Remote Display Screw terminals for max. 1 x 1.5 mm2 (16 AWG) wires included in the package.
Connection Terminals for LON/ N2 Open/ BACnet Networks Screw terminals for max. 1 x 1.5 mm2 (16 AWG) wires or 2 x BeldenR cable, 2-core twisted pair with shield .0.8 mm (20 AWG), included in the package.
BACnet Compliance BACnet Testing Laboratories™ (BTL) Listing
BACnet Interoperability Building Blocks (BIBBs):
BACnet Advanced Application Controller (B-AAC)
Protocol Implementation Conformance Statement (PICS) available on request
Agency Compliance Europe – 2004/108/EEC, EMC Directive: EN 61000-6-3, EN 61000-6-2
– 2006/95/EEC, Low Voltage Directive: EN 60730
Canada – UL Listed (PAZX7), CAN/CSA C22.2 No. 205, Signal Equipment
– Industry Canada, ICES-003
United States – UL Listed (PAZX), UL 916, Energy Management Equipment
– FCC compliant to CFR 47, Part 15, Subpart B, Class A