Belimo AM Series Direct Coupled, Non-Spring Return Actuator, 180 in-lb Minimum Torque

Direct Coupled, Non-Spring Return Actuator, 180 in-lb Minimum Torque
AM Series

Select a link under the "item" tab below to order.

Cat #Motor Drive (Default)24 VAC +/- 20%, 50/60 HZ, VDC +/- 10%VA Rating, Transformer SizingWattage Running (Holding)On/Off2-10 VDC (Default) 4-20 mA (w/500 Ω Resistor)On/Off1Floating PointStart and Span adj., Start 0.5 to 30 VDC, Span 2.5 to 32 VDCPWM adj., 0.02 to 50.0 SecondsFloating Point11 SPDT, 3 A (0.5 A inductive) @250V100 VAC to 240 VAC2-10 VDC (Default) Adjustable with MFT5 kΩ Resistive Feedback5 kΩ Resistive Feedback1S1A or S2APotentiometerEnclosure (Part No. +N4 or +N4H) with Terminal Strip
AMB24-3955.52.5 (0.4)
AMB24-3-S955.52.5 (0.4)
AMB24-SR9552.5 (0.4)
AMB24-MFT15063.5 (1.3)
Torque 180 in-lb [20 Nm] minimum
Angle of Rotation 95° (adjustable with
mechanical stops)
Fits Shaft Diameter ½" to 1.05" (centers on
½"and ¾" shafts with insert
and 1.05" without insert)
Position Indication reflective visual indicator
(snap-on)
Manual Override external push-button
Direction of Rotation external switch
Dimensions 7.47" x 3.46" x 2.49"
[189.8 x 88 x 64 mm]
Electrical Connection 3 ft, 18 GA plenum cable,
1/2" conduit fitting
Overload Protection electronic throughout
rotation
Auxiliary Switch(es) (-S) Models: 1 SPDT, 3A
(0.5A inductive) @ 250 V
adjustable 5° to 85°, Add-on:
1 or 2 SPDT, 3A (0.5 A
inductive) @ 250V one switch
adjustable 25° to 85°
Housing NEMA 2/IP54 (NEMA 1/IP20
for -T models), Enclosure
Type2
Agency Listings cULus according to UL
60730-1A/-2-14, CAN/CSA
E60730-1:02, CE according
to 2004/108/EC and
2006/95/EC