Jump to Navigation

Ashcroft CXL Differential Pressure Transmitter

Differential Pressure Transmitter
CXL

The Ashcroft® CXLdp transmitter uses the patented Ashcroft Si- Glas™ variable capacitance sensor. This MEMS sensor provides extraordinary sensitivity and long term stability. New digital compensation is accomplished using a highly reliable application specific integrated circuit (ASIC).

• Rugged ABS package capable of DIN rail or standard panel mounting
• LED power status indicator to assist in trouble shooting, correct wiring or quickly locating the instrument on a duct
• Detachable Euro style terminal block reduces wiring errors and field wiring time
• 20 standard pressure ranges all capable of withstanding 15 psi without damage or calibration change
• Digitally compensated. NIST traceable 0.4% F.S. and 0.8% F.S. accuracy models

Select a link under the "item" tab below to order.

Table 1Table 2Table 3Table 4Table 5
XXXXXXXXXX
Table 1Type Configuration
C XCXLdp
Table 2Accuracy/TC
80.8%, ±0.03%/°F
40.4%, ±0.03%/°F
Table 3Pressure Connection
MB2¼ Barbed Male
FO1⅛ NPT Female
Table 4Output Signal
424-20mA
Table 5Pressure Range
Diff. or Gauge:
P1IW0.10˝W.C.
Diff. or Gauge:
P25IW0.25˝W.C.
Diff. or Gauge:
P5IW0.50˝W.C.
Diff. or Gauge:
P75IW0.75˝W.C.
Diff. or Gauge:
1IW1.00˝W.C.
Diff. or Gauge:
2IW2.00˝W.C.
Diff. or Gauge:
2P5IW2.50˝W.C.
Diff. or Gauge:
3IW3.00˝W.C.
Diff. or Gauge:
5IW5.00˝W.C.
Diff. or Gauge:
10IW10.00˝W.C.
Diff. or Gauge:
15IW15.00˝W.C.
Diff. or Gauge:
25IW.25.00˝W.C.
Compound
P1WL±0.10˝W.C.
Compound
P25IWL±0.25˝W.C.
Compound
P5IWL±0.5˝W.C.
Compound
1IWL±1.0˝W.C.
Compound
2IWL±2.0˝W.C.
Compound
5IWL±10.00˝W.C.
Compound
10IWL±5.00˝W.C
Compound
15IWL±15.00˝W.C.
PERFORMANCE SPECIFICATIONS
Accuracy Class (F.S.): ±0.8% ±0.4%
Accuracy includes the effects of linearity, hysteresis and repeatability
Stability – Max. Change (F.S./year): ±0.25% ±0.25%
Response Time: 250 msec
ENVIRONMENTAL SPECIFICATIONS
Temperature Limits: Storage: –40 to 180°F
Operating: +0 to 160°F
Compensated Range: +35 to 130°F
(10-95% R.H. non-condensing)
Temperature Coefficients: Zero & Span ±0.03%F.S./°F
EMC: CE Compliant to EN61326: 1997+A1:
FUNCTIONAL SPECIFICATIONS
Overpressure Limits: Proof Pressure 15 psi
Burst Pressure 25 psi
Mounting Position Effect: ±1% /g (lowest range)
ELECTRICAL SPECIFICATIONS
Output Signal: 4-20mA (2 wire)
Power: 12-36 Vdc (unregulated)
Output signal is independent of power supply changes Reverse Wiring Protected Zero and Span Adjustment: Externally accessible
Zero: ±5%F.S.
Span: ±5%F.S.
PHYSICAL SPECIFICATIONS
Pressure Connections: 1⁄4˝ brass barbed fittings
1⁄8 NPT Female brass
Electrical Connection: Euro style pluggable terminal
block accepts 12-26 gauge wire
Enclosure: NEMA Type 1 Fire-retardant ABS
(meets UL 94-5VA)
LED visual indicator standard
Weight: Approx. 2.5 oz
Media: Clean, dry and non-corrosive gas
Mounting: Threaded fastener and 35mm DIN rail mount standard
Option: 1⁄2˝ plenum/conduit mounting bracket and cover kit (order part #101A213-01)
XRH: (9 point NIST Calibration Certification)

Static or velocity pressure measurement for four stations, ducts, building pressure, filter efficiency, VAV boxes or room pressurization



Main menu 2