Jump to Navigation

Action Instruments G408 DC Input Field Configurable Isolators

DC Input Field Configurable Isolators
G408

The Ultra SlimPak G408 is a DIN rail mount, DC input signal conditioner with 1800VDC isolation between input, output and power. The field configurable input and output offers flexible, wide ranging capability for DC current and voltage signals.

The input of the G408 Ultra SlimPak can be configured for any one of 12 voltage ranges from 10mV to 100V or 6 current ranges from 1mA to 100mA (see table 1). The output is linear to the input and can be set for either 0-5V, 0-10V, 0-1mA, 0-20mA or 4-20mA (for models G408-0001) and -5 to +5V or -10 to +10V (for model G408- 1001).

Wide ranging, precision zero and span pots allow 50% adjustability of offset and span turn-down within each of the 18 switch selectable ranges. For example, the 0-2mA input range could be turned down to 0-1mA and provide a full scale output signal (e.g. 4-20mA), or turned down and offset to achieve a 1-2mA/4-20mA I/O combination.

The G408 also accepts bipolar inputs (e.g. 10V range set to bipolar = -10 to +10V) and offers selectable normal or reverse operation (e.g. 4-20mA/20-4mA). The ASIC based I/O channel is optically isolated to 1800VDC and is transformer isolated from the power supply.

● Eliminates Ground Loops with 1800 VDC Input- to- Output Isolation
● Easy Field Configurable Input Ranges: 10mV to 100V, 1mA to 100mA
● Flexible Power Supply Accepts 9 to 30VDC
● Ultra Slim 12.6mm Housing Mounts on Din Rail for High-Density Installations
● ASIC Technology

Select a link under the "item" tab below to order.

Cat #Descriptions
G408-0001Field Configurable Isolator, Standard Output
G408-1001Field Configurable Isolator, Bipolar Output
Voltage Input: Range Limits: 10mV to 100V
Impedance: >100KW
Overvoltage:
400 Vrms, max. (Intermittent);
264 Vrms, max. (Continous)
Current Input: Range Limits: 1mA to 100mA
Impedance: 20W, typical
Overcurrent:170mA RMS, max.
Overvoltage: 60VDC
Zero Turn-Up: 50% of full scale input
Span Turn-Down: 50% of full scale input
Common Mode (Input to Ground): 1800 VDC, max.
Output (G408-0001)
Voltage Output: Output:0-5V, 0-10V
Source Impedance: <10W
Drive: 10mA, max.
Current Output: Output: 0-1mA,4-20mA,0-20mA
Source Impedance: >100KW
Compliance:0-1mA: 7.5V, max (7.5KW)
4-20mA: 12V, max (600W)
0-20mA: 12V, max (600W)
Output (G408-1001) Voltage Output: Output: -5V to +5V, -10 to +10V
Source Impedance: <10W
Drive: 10mA, max.
LED Indication (green) Input Range: >110%(approx) input:8Hz flash
< -10%(approx) input: 4Hz flash
Accuracy (Including Linearity, Hysteresis): <2mA/<20mV: ± 0.35% of full scale, typical; 0.5%,max.
>2mA/>20mV: ± 0.1% of full scale, typical; 0.2%, max.
Response Time (10-90%): 200mSec., typical
EMC Compliance (CE Mark): Emissions: EN50081-1
Immunity: EN50082-2
Safety:EN50178
Mean Time Between Failures: 60K Hours
Humidity (Non-Condensing): Operating: 15 to 95%(@ 45‹C)
Soak:90% for 24 hours (@ 65‹C)
Temperature Range: Operating: 0 to 55°C (32 to 131°F)
Storage: -25 to 70°C (-13 to 158°F)
Wire Terminal: Screw terminals for 12-22AWG
Power: Consumption: 1.5W typical, 2.5W max.
Range: 9 to 30VDC
Weight: 0.5 lbs.
Agency Approvals: CSA certified per standard C22.2, No. 0-M91 and 142- M1987 (File No. LR42272).
UL recognized per standard UL508 (File No.E99775).
CE Conformance per EMC directive 89/336/EEC and Low Voltage 73/23/EEC (Input < 75VDC, only).