Jump to Navigation

Action Instruments AP1080/AP1090 DC Input, Field Configurable Limit Alarms

DC Input, Field Configurable Limit Alarms
AP1080/AP1090

Action Pak models AP1080 single setpoint and AP1090 dual setpoint limit alarms offer flexible, wide-ranging DC input capability. Voltage spans from 10mV to 200 volts and current spans from 1mA to 100mA can be field configured. Bipolar inputs are also accepted. Both models offer configurable latching, failsafe and HI/LO operation. The AP1080 and AP1090 also include 0.25%-50% adjustable deadbands and selectable 120/240VAC operation.

● Selectable 120/240VAC Operation (9 to 30 VDC Available)
● Field Configurable Input Ranges for DC Voltage and Current
● Setpoint(s)Programmable HI or LO
● Exclusive“Dynamic Deadband” Prevents False Trips
● Selectable Failsafe/Latching Operation

Select a link under the "item" tab below to order.

Cat #Descriptions
1080-2000-1Field Configurable Single Limit Alarm, AC Powered
1080-2000-DField Configurable Single Limit Alarm, DC Powered
1090-2000-1Field Configurable Dual Limit Alarm, AC Powered
1090-2000-DField Configurable Dual Limit Alarm, DC Powered
Voltage Input: Range: 10mV to 200V
Impedance: >100K Ohmns
Overvoltage: Intermittent, 400Vrms Continuous, 264 Vrms
Current Input: Full Scale Range: 1mA to 100mA
Impedance: 20 Ohms, typical
Overcurrent: 200mA, max
Overvoltage: 60VDC
Common Mode (Input toGround): 1500VDC, max
LED Indications: Input Range (Green)
>100% input: 8Hz flash
<0% input: 4Hz flash
Setpoint (Red) Tripped: Solid red
Safe: Off
Limit Differential: >50mV/5mA: .25% to 50% of span
<50mV/5mA: 1% to 50% of span
Response Time: Dynamic Deadband: Relay status will change when proper setpoint/process condition exists uninterrupted for 100ms
Normal Mode (analog filtering): <250ms, (10-90%)
Setpoint: Effectivity: Setpoints are adjustable over 100% of the selected input span.
Weight: AP1080: .46lbs; AP1090: .62lbs
Agency Approvals: CSA certified per standard C22.2, No. M1982.
UL recognized per standard UL508.
EMC Compliance (CE Mark): Emissions: EN50081-1
Immunity: EN50082-2
Safety:EN50178
Mean Time Between Failures: 60K Hours
Humidity (Non-Condensing): Operating: 15 to 95%(@ 45‹C)
Soak:90% for 24 hours (@ 65‹C)
Temperature Range: Operating: 0 to 55°C (32 to 131°F)
Storage: -25 to 70°C (-13 to 158°F)
Wire Terminal: Screw terminals for 12-22AWG
Power: Consumption: 1.5W typical, 2.5W max.
Range: 9 to 30VDC
Weight: 0.5 lbs.
Agency Approvals: CSA certified per standard C22.2, No. 0-M91 and 142- M1987 (File No. LR42272).
UL recognized per standard UL508 (File No.E99775).
CE Conformance per EMC directive 89/336/EEC and Low Voltage 73/23/EEC (Input < 75VDC, only).


Main menu 2